Бюджетный охладитель воды SIC-W-EB

Дополнительная информация:
Оставить заявку
0%

    Характеристики

    Модель SIC-5W-EB SIC-10W-EB
    Refrigerant Capacity kW 10 20
    kcal/hr 8,609 17,217
    Compressor Type Scroll
    Input power (kW) 3.3 6.6
    Input power (HP) 5 8
    Refrigerant Filling Volume (kg) 3.1 6.2
    Control Mode Capillary
    Type R410A
    Evaporator Type Tube style
    Condenser Type Tube-in-shell style
    Inlet/outlet pipe (inch) 1.5 1.5
    Cooling water flow (L/min) 65 90
    Water Tank Capacity L 55 145
    Water pump (50Hz) Power (kW) 0.37 0.75
    Pump flow (l/min) 60
    Working pressure (Bar) 2.0
    Total power kW 3.67 7.35
    Pipe Coupling Chilled Water Outlet (inch) 1
    Chilled Water Inlet (inch) 1
    Water Tank Drainage Port (inch) 1/2
    Water Tank Overflow Port (inch) 1/2
    Protective Devices Compressor Built-in protective switch/Overload Relay
    Pump Overload Relay
    Refrigerant loop High/low pressure controller
    Power ЗФ, 400VAC, 50Hz
    Measures Exchange 1 kW=860 Kcal/hr 1RT=3,024 Kcal/hr 10,000 Btu/hr=2,520 Kcal/hr
    Цена
     
    ■ Features

    • Cooling range 7~25°C.
    • Stainless steel insulated water tank, with prolonged service life and free of contanmination.
    • Adopt R410 A refrigerant with good refrigeration effect.
    • Refrigeration loop controlled by high and low pressure switches for accurate detection of system pressure.
    • Compressor and pump overload protection.
    • Shell and tube condenser with quick heat conduction and good dissipation effect.
    • Adopt tube and shell evaporator.The copper pipe is directly mounted on water tank that is economical and practical.
    • Adopt renowned brand of original precision temperature- controlled meter with an accuracy of ±0.1°C.


    Рисунок2.jpg



    ■ Application

    SIC-W-EB series are applicable for cooling moulds to reduce products molding cycle time; also they are available in the cooling of equipments in order to maintain a normal temperature. Besides, they are suitable for other industries with the need of cooling.


    Structure of Water-cooled Models

    Рисунок7.jpg

    Рисунок8.jpg
    Working Principle

    SIC-W-EB water-cooled water chiller mainly consists of compressor, condenser, capillary and tube evapo­rator. Adopting single-stage vapor compression refrigerating system, gas-liquid conversion of refrigerant, and the principle of heat adsorption and release, it achieves the cooling effect.
    When SIC-W-EB water-cooled water chiller starting up, compressor (A) starts working. Refrigerant is com­ pressed into high temperature high pressure gas, and then be cooled when passing through condenser (D) and changed into liquid. Heat is taken away by the cooling water. The liquid high pressure refrigerant passes through the capillary (F), and partial refrigerant is changed into gas under reduced pressure. At this time, the refrigerant is mixed with gas and liquid, which cools down the chilled water into required tem­ perature after passing through the tube evaporator (I). By heat adsorption, the liquid refrigerant changes to gas and returns the compressor for this circulation.

    Рисунок3.jpg


    Outline Drawings

    Рисунок4.jpg

    Рисунок5.jpg

    Рисунок6.jpg

    Похожие товары